Performance characteristics:
The main purpose of the high efficiency exhaust outlet is to filter the air discharged from the biological laboratory or negative pressure isolation ward through the high efficiency air filter to ensure the safety of the gas discharged and meet the requirements of the code.
Settings:
Single filter module 300-3000CMH air volume
In situ disinfection
Differential pressure gauge
Field scanning device
Optional configuration:
Closed valve
Filter segment (primary/middle)
Technical parameters:
Filtration efficiency: H14 (99.995%)
Applicable temperature: up to 60℃
Resistance pressure: ± 2500Pa positive pressure
Under 1000Pa pressure, the leakage rate is less than 0.1%
Overall material: SUS304
Applications:
Used in biological laboratories, biopharmaceutical clean rooms, infectious diseases negative pressure isolation wards, etc. Installation methods include top installation, side wall installation and isolation bed under the bed installation, exhaust methods include side exhaust mode and top exhaust mode, to meet the diversified space requirements of customers' equipment mezzanine.